Thumbnail
Access Restriction
Subscribed

Author Yongsug Suh ♦ Steinke, J. ♦ Steimer, P.
Source IEEE Xplore Digital Library
Content type Text
Publisher Institute of Electrical and Electronics Engineers, Inc. (IEEE)
File Format PDF
Copyright Year ©2005
Language English
Subject Domain (in DDC) Natural sciences & mathematics ♦ Physics ♦ Electricity & electronics ♦ Technology ♦ Engineering & allied operations ♦ Applied physics
Subject Keyword Thyristors ♦ Switching converters ♦ Voltage source inverters ♦ Drives ♦ Loss measurement ♦ Inverters ♦ AC machine ♦ Multilevel converters ♦ Filters ♦ Efficiency ♦ Rectifiers ♦ Switching loss ♦ Medium voltage ♦ Power system reliability ♦ Current source inverter
Abstract This paper calculates and compares the efficiency and loss distribution in three most popular state-of-the-art types of medium voltage drive systems; current source drive with active front-end rectifier, current source drive with 18-pulse thyristor rectifier, and three-level voltage source drive with 12-pulse/24-pulse diode rectifier. Based on the proposed simple and accurate method of calculating switching losses, snubber and filter losses, three-level voltage source drive system has been found to produce the highest efficiency of 98.77% under the rated load of 1.6 MW
Description Author affiliation: ABB Switzerland Ltd., Turgi (Yongsug Suh; Steinke, J.; Steimer, P.)
ISBN 9075815093
Educational Role Student ♦ Teacher
Age Range above 22 year
Educational Use Research ♦ Reading
Education Level UG and PG
Learning Resource Type Article
Publisher Date 2005-09-11
Publisher Place Germany
Rights Holder EPE Association
Size (in Bytes) 3.91 MB


Source: IEEE Xplore Digital Library