Subject Keyword Pulse Width Modulation (PWM) ♦ Unit vector ♦ Power system harmonics ♦ Converters ♦ Digital Signal Processor (DSP) ♦ Voltage Source Converter (VSC) ♦ Steel ♦ Power conversion ♦ Voltage control ♦ Power harmonic filters ♦ Power Quality (PQ) ♦ Furnaces ♦ Power quality ♦ IEEE 519-1992 Std. ♦ Active filters ♦ Total Demand Distortion (TDD) ♦ Three level converter ♦ Automatic voltage control ♦ STATCOM ♦ induction furnace
Abstract The paper explains the power quality study conducted in a 4 MW mini steel plant, having fault level of 250 MVA, to investigate the critical electrical problems caused by the harmonics and the development of a STATCOM as a solution for harmonic mitigation. A 500 kVAR STATCOM is realized with a current controlled three level voltage source converter (VSC). The hardware configuration and the control strategy have been dealt in detail. Site installation and experimental results demonstrating STATCOM's performance are also presented.
Description Author affiliation: Centre for Dev. of Adv. Comput., Trivandrum (Unnikrishnan, A.K.; Aby, J.; Subhash, J.T.G.)
ISBN 9789275815108
Educational Role Student ♦ Teacher
Age Range above 22 year
Educational Use Research ♦ Reading
Education Level UG and PG
Learning Resource Type Article
Publisher Date 2007-09-02
Publisher Place Denmark
Rights Holder EPE Association
Size (in Bytes) 481.63 kB
Page Count 7
Starting Page 1
Ending Page 7


Source: IEEE Xplore Digital Library